Setup Guide

Completing the Ground Wire Installation
After you have installed the S6010-ON switch in a rack, complete the installation of
the ground wire.
You previously installed the GND lug and bracket assembly, with ground wire
attached, to the S6010-ON chassis (see
Installing the Ground Lug and Bracket Assembly).
You must supply:
One two-hole UL-certified GND lug (to attach ground wire to rack).
Two NEC (National Electric Code) compliant screws (to attach GND lug to rack)
Anti-oxidant compound.
Crimping tool.
1 Measure and cut a length of wire sufficient to reach between the system-
installed GND lug and the rack-end GND lug.
2 Attach the end of the wire to the rack-end GND lug.
a Coat the bare end of the wire with an anti-oxidant compound.
b Insert the end of the wire into the lug.
c Crimp the lug end to secure the connection.
Figure 10. Ground Wire End and GND Lug Opening
3 Install the second GND lug in compliance with NEC guidelines at the desired
location on your rack to be used for grounding the switch.
Install the Hardware 16