Figure 15. Front-rack conguration installation
Ground wire installation
After you have installed the S6010-ON switch in a rack, complete the installation of the ground wire.
You previously installed the GND lug and bracket assembly, with ground wire attached, to the chassis, see Installing the Ground Lug and
Bracket Assembly.
Supply the following items:
• One 2-hole UL-certied GND lug to attach ground wire to rack
• Two National Electric Code (NEC) compliant screws to attach the GND lug to the rack
• Anti-oxidant compound
• Crimping tool
1 Measure and cut a length of wire sucient to reach between the system-installed GND lug and the rack-end GND lug.
2 Attach the end of the wire to the rack-end GND lug.
a Coat the bare end of the wire with an anti-oxidant compound.
b Insert the end of the wire into the lug.
c To secure the connection, crimp the lug.
S6010–ON installation