Reference Guide

FCoE Transit | 363
Figure 16-11. Configuration Example: FCoE Transit on an S5000 Switch
In Figure 16-11, DCBx and PFC are enabled on the FIP snooping bridge and on the FCF ToR switch. On
the FIP snooping bridge, DCBx is configured as follows:
A server-facing port is configured for DCBx in an auto-downstream role.
An FCF-facing port is configured for DCBx in an auto-upstream or configuration-source role.
The DCBx configuration on the FCF-facing port is detected by the server-facing port and the DCB PFC
configuration on both ports is synchronized. For more information about how to configure DCBx and PFC
on a port, refer to Data Center Bridging (DCB).
Figure 16-12 shows how to configure FIP snooping on FCoE VLAN 10, on an FCF-facing port (0/50), on
an ENode server-facing port (0/1), and to configure the FIP snooping ports as tagged members of the FCoE
VLAN enabled for FIP snooping.