Figure 4. Attaching Mounting Brackets into a Two-Post Rack or Cabinet
1.
View from the chassis I/O side 2. Connect to the Rack or Cabinet (ears)
3. Screws 4. Screws
5. Connect to the Rack or Cabinet (ears) 6. Power Supply
Two-post installation
Ensure that there is adequate clearance surrounding the rack or within the cabinet to permit access and airflow.
To install a system into a two-post 19-inch equipment rack using the already attached mounting brackets, follow these steps.
NOTE:
Dell Technologies recommends using one person to hold the S4810–ON chassis in place while another person
attaches the brackets to the posts.
Attach the bracket “ears” to the rack or cabinet posts using the two screws for each bracket. Ensure that the screws are tightened firmly.
14