Figure 19. S4048T-ON PSU-side view
1 PSU1 2 Fan modules
3 RS-232/RJ-45 serial console port 4 PSU2
5 10/100/1000BaseT Ethernet management port
Fan module installation
The fan modules in the S4048T-ON are eld replaceable.
Module slot 1 is on the left side of the chassis, module slot 2 is in the middle of the chassis, and module slot 3 is on the right side of the
chassis.
CAUTION
: DO NOT mix airow directions. All fans must use the same airow direction—reverse or normal. If you mix the airow
direction, to avoid damage to the switch, you must correct the mixed airow.
1 Take the fan module out of the shipping box.
2 Use the grab handle to slide the module into the bay.
Figure 20. S4048T-ON fan module installation
1
1—Fan module
Fan module replacement
CAUTION
: Complete steps 2 and 3 within one minute or the system powers down.
1 Use the red-marked grab handle to slide the fan module out of the bay.
2 Use the red-marked grab handle on the replacement module to slide it into the bay.
3 Ensure that the module is secure.
34
Fans