Setup Guide

Parameter Specications
Storage humidity 5 to 95%, non-condensing
Maximum thermal output 1153.265 BTU/hr
Maximum operational altitude 10,000 feet (3,048 meters)
Maximum non-operational altitude No performance degradation to 35,000 feet (10,668 meters)
Shock Meets Bellcore Zone 4 earthquake requirements (MIL-STD-810)
Table 8. AC power requirements
Parameter Specications
Power supply 100–240 VAC 50/60 Hz
Maximum current draw per system
5.8 A @ 398.02 watts/100vac
2.9 A @ 398.02 watts/200vac
Maximum power consumption 460 Watts
Typical power consumption 338 Watts
Reliability MTBF 355.178 hours
IEEE standards
The S4048–ON complies with the following IEEE standards:
802.3ab Gigabit Ethernet (1000BASE-T)
802.3ae 10 Gigabit Ethernet (10GBASE-X)
802.3ba 40 Gigabit Ethernet (40GBase-SR4, 40GBase-CR4) on optical ports
802.3u Fast Ethernet (100BASE-TX)
802.3z Gigabit Ethernet (1000BASE-X)
Agency compliance
The S4048–ON is designed to comply with the following safety and agency requirements.
Network Equipment Building Systems Compliance
Use shielded cables for ports from 0 to 48. Ground the shields at both ends.
Use only reverse airow congurations in a NEBS-compliant installation.
Fit the power supplies and fan modules with lter kits. Replace the fan lters on a regular basis.
Use this equipment with an external, second-level 6 kV lightning surge protective device (SPD) at the AC input of the building.
Use an SPD with the AC power connections to protect the AC power supplies from damage from excessive power line surges.
In order to comply with the GR-1089 Lightning Criteria for Equipment Interfacing with AC Power Ports, use an SPD at the AC input of
the router.
WARNING
: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap
when handling the S4048-ON and its components.
Specications 39