Setup Guide
Fans
The S4048–ON comes from the factory with one PSU and three fan modules installed in the chassis. The fan modules and the power
supplies, which have integrated fans, are hot-swappable.
NOTE: To run the switch, the three fan slots must have operating fan units. If you do not install a module in each slot, the switch
shuts down in one minute.
In addition to the power supply modules, you can order and install fan modules separately.
The S4048-ON supports two airow direction options. Do not mix airow types in a chassis; you can use only a single airow direction in a
chassis. If the airow directions are mismatched, the S4048-ON powers down in one minute.
• Normal—airow is from the I/O-side to the PSU-side
• Reversed—airow is from the PSU-side to the I/O-side
All fans and PSUs in a conguration must be in the same airow direction.
Environmental factors can decrease the amount of time required between fan replacements. Check the environmental factors regularly. An
increase in temperature and/or particulate matter in the air might aect performance; for example, new equipment installation.
CAUTION
: Check the fans at six-month intervals and replace them as necessary. Regularly monitor the speeds of the cooling
fans in order to accurately determine replacement intervals.
Topics:
• Components
• Fan module installation
• Fan module replacement
• After S4048–ON installation
Components
The following are the S4048–ON fan components:
• S4048–ON AC power supply with integrated fan module
• S4048–ON AC power supply with integrated fan module—reverse ow
Figure 20. S4048–ON fan modules