CAUTION: DO NOT mix airflow directions. All fans must use the same airflow
direction (I/O to Utility or Utility to I/O).
CAUTION: Check the fans at six-month intervals and replace them as
necessary. To accurately determine replacement intervals, regularly monitor
the speeds of the cooling fans.
Installing the SFP+ Optics
The S3048–ON has four small form-factor pluggable plus (SFP+) optical ports.
For a list of supported optics, refer to the S3048–ON data sheet at www.dell.com or
contact your Dell Networking representative.
CAUTION: ESD damage can occur if the components are mishandled. Always
wear an ESD-preventive wrist or heel ground strap when handling the S3048–
ON and its components.
WARNING: When working with optical fibers, follow all the warning labels and
always wear eye protection. Never look directly into the end of a terminated
or unterminated fiber or connector as it may cause eye damage.
1 Position the optic so it is in the correct position. The optic has a key that
prevents it from being inserted incorrectly.
2 Insert the optic into the port until it gently snaps into place.
NOTE: When you cable the ports, be sure not to interfere with the airflow
from the small vent holes above and below the ports.
Supply Power and Power Up the System
Supply power to the S3048–ON after the chassis is mounted in a rack or cabinet.
Dell Networking recommends re-inspecting your system prior to powering up.
Verify that:
• The equipment is properly secured to the rack.
• The equipment rack is properly mounted and grounded.
• The ambient temperature around the unit (which may be higher than the room
temperature) is within the limits specified for the S3048–ON.
• There is sufficient airflow around the unit.
• The input circuits are correctly sized for the loads and that you use sufficient
overcurrent protection devices.
• All protective covers are in place.
Install the Hardware 17