Reference Guide

Table 12. Maximum altitude specifications
Maximum altitude Specifications
Operating Mil-Std 810G method 500.6, Proc. II, air carriage, 15,000 ft for 1 hour after
stabilization
Storage Mil-Std 810G method 500.6, Proc. I, 40,000 ft for 1 hour after stabilization
Standard operating temperature
Table 13. Standard operating temperature specifications
Standard operating temperature Specifications
Continuous operation (for altitude less than 950 m or 3117
ft)
+5°C–45°C (41°F–113°F) with no direct sunlight on the equipment
NOTE: The 150W CPU support is only up to 35°C.
NOTE: GPU continuous operation is supported up to 30°C.
NOTE: GPU continuous operation is supported up to 45°C with
optional fan booster kit.
Expanded operating temperature
Table 14. Expanded operating temperature specifications
Expanded operating temperature Specifications
Continuous operation 5°C to 45°C at 5% to 85% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C to
35°C), the system can operate continuously in temperatures as
low as 5°C and as high as 45°C.
For temperatures between 35°C and 45°C, de-rate maximum allowable
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
≤ 1% of annual operating hours –5°C to 55°C at 5% to 90% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C to
35°C), the system can operate down to –5°C or up to 55°C for a
maximum of 1% of its annual operating hours.
NOTE: GPU expanded operating temperatures is up to 37°C for
selected configurations.
NOTE: GPU expanded operating temperatures is up to 50°C for
selected configurations with optional fan booster kit.
For temperatures between 45°C and 55°C, de-rate maximum allowable
temperature by 1°C per 125 m above 950 m (1°F per 228 ft).
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD
panel and in the System Event Log.
Expanded operating temperature restrictions
Do not perform cold start below -15C Per IEC 60945.
The operating temperature specified is for a maximum altitude of 950 m.
Redundant power supplies are required.
10
PowerEdge XR2 technical specifications