User manual
Chapter 3 – Using the ePower Web Interface
28 ePower Power Distribution Unit User Manual, Revision 1.1
Banks and Outlets Pane
This is the Home page for the ePower Web interface. Displays status and
allows access to the following bank and outlet controls:
• Select a bank name to access the Bank Controls pane for that bank.
• Select an outlet name to access the Outlet Controls pane
for that outlet.
• Use the State drop-down menu to turn outlets On, Off,
or begin Reboot.
The Bank Controls pane (refer to Figure 3-3) includes the Alerts tab:
• Enabled – Select to enable the High Current Alert for that bank.
• High Current Alert – Enter Threshold and Maximum
Grace Period.
• Email Notification List – Enter a comma-separated list of email
address to notify you if the high current limit is reached. Email alerts
are also entered in the Setup Logging pane. The following are sample
email alerts:
– Input Critical Alert Example
Load on Input 1 Line A (32.5 A) exceeds 100% safety limit (32.0 A)
– Input Warning Alert Example
Load on Input 1 Line B (41.2 A) exceeds 80% safety limit (40.0 A)
– Input User-Defined High Current Alert Example
Load on Input 1 Line C (22.8 A) exceeds user-defined high current limit (20.5 A)
– Bank Critical Alert Example
Load on Bank 1 (21.5 A) exceeds 100% safety limit (20.0 A)
– Bank Warning Alert Example
Load on Bank 2 (17.2 A) exceeds 80% safety limit (16.0 A)
– Bank User-Defined High Current Alert Example
Load on Bank 3 (6.8 A) exceeds user-defined high current limit (4.0A)