Table 12. Particulate contamination specifications
Particulate contamination Specifications
Air filtration Data center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit.
NOTE: This condition applies to data center environments only. Air
filtration requirements do not apply to IT equipment designed to be
used outside a data center, in environments such as an office or
factory floor.
NOTE: Air entering the data center must have MERV11 or MERV13
filtration.
Conductive dust Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE: This condition applies to data center and nondata center
environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less
than 60% relative humidity.
NOTE: This condition applies to data center and nondata center
environments.
Table 13. Gaseous contamination specifications
Gaseous contamination Specifications
Copper coupon corrosion rate <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver coupon corrosion rate <200 Å/month as defined by AHSRAE TC9.9.
NOTE: Maximum corrosive contaminant levels measured at 50% relative humidity.
Standard operating temperature
Table 14. Standard operating temperature specifications
Standard operating temperature Specifications
Continuous operation (for altitude less than 950 m or
3117 ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight on the
equipment.
Humidity percentage range 10% to 80% Relative Humidity with 29°C (84.2°F) maximum dew
point.
Expanded operating temperature
Table 15. Expanded operating temperature specifications
Expanded operating temperature Specifications
Continuous Operation 5°C40°C at 5% to 85% RH with 29°C dew point
NOTE: Outside the standard operating temperature (10°C35°C),
the system can operate continuously in temperatures as low as 5°C
and as high as 40°C.
For temperatures 35°C40°C, derate maximum allowable dry bulb
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
Less than or equal to 1% of annual operating hours 5°C45°C at 5% to 90% RH with 29°C dew point
Technical specifications 9