EPP Event Messages
EPP001
Message Unable to use the Extended Power Performance (EPP) feature on chassis.
Detailed
Description
The Extended Power Performance cannot be used unless chassis has six EPP
capable PSUs, Configure the Power Redundancy Policy to Grid Redundancy &
MPCM, DPSE, SBPM and Fresh Air features should be disabled.
Recommended
Response Action
Make sure that chassis has six EPP capable PSUs, Configure the Power Redundancy
Policy to Grid Redundancy & MPCM, DPSE, SBPM and Fresh Air features should be
disabled. Then enable the EPP feature.
Category System Health (EPP = Extended Power Performance)
Severity Severity 2 (Warning)