Reference Guide

CMC8543
Message The CMC arg1 has reset because the thermal threshold was exceeded.
Arguments arg1 = slot id
Detailed
Description
The CMC specified in the message has reset because of thermal issues.
Recommended
Response
Action
Do the following: 1) Review the Hardware Log and check if there are fans that are
not functioning properly. 2) Replace the fans that are not functioning properly. 3) If
all the fans are functioning, check the chassis temperature in the CMC Web
Interface or by using RACADM. When the fans are functioning properly and the
chassis temperature is too high, the ambient air temperature is too high or the air
inlets are not receiving sufficient air.
Category Audit (CMC = Chassis Management Controller)
Severity Severity 1 (Critical)
Filter
Visibility
IPMI
Alert
SNMP
Alert
Email
Alert
Remote System
Log
WS
Eventing
iDRAC
CMC
LC Log LCD OS Log Power
Off
Power
Cycle
Reset Chassis Event
Proxy
iDRAC *
CMC * *
CMC8545
Message Detected a missing process failover condition detected. Process = arg1 .
Arguments arg1 = process name
Detailed
Description
A firmware error has occurred causing a CMC failover. The process identified in the
message was not detected. The CMC will restart automatically.
Recommended
Response
Action
No response action is required. If multiple failovers occur, contact your service
provider.
Category Audit (CMC = Chassis Management Controller)
Severity Severity 1 (Critical)