Reference Guide

RAC1072
Message Unable to set maximum non critical threshold value of arg1 , because the value
entered is less than, or equal to the minimum critical threshold value.
Arguments arg1 = System Board Inlet Temp
Detailed
Description
The maximum non critical threshold value identified in the message cannot be set,
because the value entered is less than or equal to the minimum critical threshold
value.
Recommended
Response
Action
Check the minimum critical threshold level using an appropriate RACADM
command. For example, to view the minimum critical threshold value of a sensor,
run the racadm getsensorinfo command at the command line interface, and then
retry the operation. For more information about other RACADM commands, run
the racadm help command.
Category Configuration (RAC = RAC Event)
Severity Severity 2 (Warning)
Filter
Visibility
IPMI
Alert
SNMP
Alert
Email
Alert
Remote System
Log
WS
Eventing
iDRAC
CMC
LC Log LCD OS Log Power
Off
Power
Cycle
Reset Chassis Event
Proxy
iDRAC
CMC
RAC1073
Message Unable to reset the threshold value of sensor arg1 because the capability to reset
this sensor threshold value is not supported.
Arguments arg1 = sensor name
Detailed
Description
The threshold value of the sensor identified in the message cannot be successfully
set because the capability reset the sensor threshold value is not supported.
Recommended
Response
Action
No response action is required. For more information about resetting the threshold
level of a sensor, run the "racadm getsensorinfo" command at the command line
interface (CLI), and then retry the operation.
Category Configuration (RAC = RAC Event)
Severity Severity 3 (Informational)
1403