CLI Guide

You cannot default one value and set another. In other words, if you set the minimum warning threshold value to the default value, you are
also selecting the default value for the maximum warning threshold value.
NOTE: The capabilities for managing sensors vary by systems.
Specify a value for minimum and maximum warning thresholds
To specify values for the temperature probe warning thresholds, you must specify the number of the probe you are conguring and the
minimum and/or maximum warning threshold value. In the following example, the probe that is being congured is probe 4:
omconfig chassis temps index=4 minwarnthresh=11.2 maxwarnthresh=58.7
or
omconfig mainsystem temps index=4 minwarnthresh=11.2 maxwarnthresh=58.7
When you issue the command and the system sets the values you specify, the following message is displayed:
Temperature probe warning threshold(s) set successfully.
Omcong Chassis Volts Or Omcong Mainsystem Volts
Use the omcong chassis volts or omcong mainsystem volts command to set voltage probe warning thresholds. As with other
components, you can view both warning and failure threshold values, but you cannot set failure threshold values. The system manufacturer
sets the minimum and maximum values for the failure thresholds.
Valid parameters for voltage warning thresholds
The following table displays the valid parameters for setting voltage warning threshold values.
NOTE
: Threshold values that you can set vary from one system conguration to another.
Table 58. Valid Parameters Of Omcong Chassis Volts Or Omcong Mainsystem Volts
name=value pair Description
index=<n> Probe index (specify).
warnthresh=default Sets minimum and maximum warning threshold values to default.
minwarnthresh=<n> Sets minimum warning threshold value (three decimal places).
maxwarnthresh=<n> Sets maximum warning threshold value (three decimal places).
Specify A Value For Minimum And Maximum Warning Thresholds
To specify values for the voltage probe warning thresholds, you must specify the number of the probe you are conguring and the
minimum and/or maximum warning threshold values.
In the following example, the probe being congured is probe 0:
omconfig chassis volts index=0 minwarnthresh=1.900 maxwarnthresh=2.250
or
omconfig mainsystem volts index=0 minwarnthresh=1.900 maxwarnthresh=2.250
94
Omcong Managing Components Using The Instrumentation Service