126 omconfig: Managing Components Using the Instrumentation Service
omconfig chassis temps/omconfig mainsystem temps
Use the omconfig chassis temps or omconfig mainsystem temps command
to set warning thresholds for temperature probes. As with other components,
you can view both warning and failure threshold values, but you cannot set
failure threshold values. Your system's manufacturer sets the minimum and
maximum failure threshold values.
NOTE: Threshold values that you can set vary from one system configuration
to another.
Valid Parameters for Temperature Warning Thresholds
Table 4-14 shows the valid parameters for setting temperature warning
thresholds:
Setting Minimum and Maximum Warning Threshold Values
If you want to set both the upper and lower temperature warning threshold
values to the recommended default value, type:
omconfig chassis temps index=0 warnthresh=default
or
omconfig mainsystem temps index=0 warnthresh=
default
You cannot default one value and set another. In other words, if you set the
minimum warning threshold value to the default value, you are also selecting
the default value for the maximum warning threshold value.
NOTE: The capabilities for managing sensors vary by systems.
Table 4-14. omconfig chassis temps/omconfig mainsystem temps
name=value pair Description
index=<n> Number of the probe or probe index (must be
specified).
warnthresh=default Sets the minimum and maximum warning threshold
values to default.
minwarnthresh=<n> Sets the minimum warning threshold values (1 decimal
place).
maxwarnthresh=<n> Sets the maximum warning threshold values (1 decimal
place).