Users Guide
Clear Alert Number: None.
Related Alert Number: None.
Local Response Agent (LRA) Alert Number: None.
SNMP Trap Number: 1151. See "SNMP Support for Storage Management Alerts" for more information.
2171
Description: The controller battery temperature is above normal.
Cause: The room temperature may be too hot. The system fan may also be degraded or failed.
Action: Verify that the room temperature is normal. See the hardware documentation for acceptable operating temperatures. Verify that system components
such as the fan are functioning properly.
Severity: Warning/Noncritical. See "Alert Severity Levels" for more information.
Clear Alert Number: 2172. The clear alert is generated when the conditions producing the current alert have returned to normal.
Related Alert Number: None.
Local Response Agent (LRA) Alert Number: 2100
SNMP Trap Number: 1153. See "SNMP Support for Storage Management Alerts" for more information.
2172
Description: The controller battery temperature is normal.
Cause: This alert is provided for informational purposes.
Action: None.
Severity: OK/Normal/Informational. See "Alert Severity Levels" for more information.
Clear Alert Status: Alert 2172 is a clear alert for alert 2171.
Related Alert Number: None.
Local Response Agent (LRA) Alert Number: None.