Complete Syntax
omconfig storage enclosure action=setalltempprobes
controller=id enclosure=<ENCLOSUREID> minwarn=n
maxwarn=n
where id is the controller ID. The <ENCLOSUREID> variable specifies the
enclosure.
Example Syntax
For example, you may want to specify the minimum and maximum warning
thresholds for all temperature probes to 10 and 40
° Celsius.
Example for SAS Controllers
In this example, the temperature probes reside in enclosure 3 attached to
connector 2 on controller 1. To set the thresholds for all temperature probes
to 10 and 40
° Celsius, enter:
omconfig storage enclosure action=setalltempprobes
controller=1 enclosure=2:3 minwarn=10 maxwarn=40
omconfig Reset All Temperature Probe Thresholds
Use the following omconfig command syntax to reset the minimum and
maximum warning temperature thresholds back to their default value for all
temperature probes in the enclosure.
NOTE: This command is not supported on SCSI RAID controllers.
Complete Syntax
omconfig storage enclosure action=
resetalltempprobes controller=id enclosure=
<ENCLOSUREID>
where id is the controller ID. The <ENCLOSUREID> variable specifies the
enclosure.
Example Syntax
For example, you may want to reset the thresholds for all temperature probes
in enclosure 2 on controller 1.