Users Guide
• Demand — Amount of power a device requests to accommodate its workload.
• Estimated maximum power (Estimated max power) — The maximum power consumption allocation
estimated for a device. The estimated max power is considered the peak power consumption by a
device.
Dynamic power caps enable all devices to execute workloads without requiring more power than the
overall power cap assigned to the group. When choosing a dynamic power cap, remember:
• If lower-priority devices require more power to maintain their cap, they may receive more power than
higher-priority devices.
• If the power cap is too restrictive and the group power consumption exceeds the power cap, an error
event occurs for the policy. If this occurs frequently, reconsider your power allocations, or adjust
workloads accordingly.
• If fluctuations in device power requirements occur after the power cap is successfully established,
then a device that requires more power may not receive it if the power cap of another device in the
policy would be violated. To force one or more devices in a policy to a lower cap, create a static
power policy for the device at a lower level (rack or chassis). The most restrictive power cap of the
overlapping policies is applied to the device.
• If there is excess available power (known as headroom) after all power capping requirements are met,
the excess power is dynamically allocated according to the priority and demand of each device in the
power policy.
Power Policy Capabilities
Power Center defines the following statuses of power policy capabilities for the devices:
• Unknown — Shown for unsupported devices or devices that were never connected to Power Center.
• None — No power policy capability. You cannot set any policy on the device.
• Monitor — With power monitoring capability only.
• Monitor & Capping — With power monitoring and capping capabilities.
• Monitor and Upgradable — With power monitoring capability, and can be upgraded to have power
capping capability.
You can find this power policy capability status in the Power Capability column of the Devices page.
For servers that comply with Dell iDRAC7, when there is a power policy capability change due to a license
change, Power Center changes its information in the management console within 24 hours. There are
two scenarios:
Scenario 1 — The license expires or is not imported
In this case, the following happens:
• If a policy exists on the devices, a "Server Capabilities Changed" event is generated.
• The Policies tab of the devices is set to disabled in the Groups page.
• The power capability status of the devices is set to "None" in the Devices page.
83