A power policy is a set of configurations used to manage the power cap for a device or group. A policy is useful for
power management in different situations. For example, you can set up a policy to:
• Make sure power consumption does not exceed the capacity of the circuit.
• Schedule power usage according to the workload of the device/group. For example, you can set an aggressive
cap when the workload is low, enabling a reduction of power use for your data center.
• Increase rack density. For example, you could monitor current power consumption on a rack with ten device to
estimate how many additional devices you can add to the rack. Then, you can establish a power policy to cap
the total power consumption of the rack after the devices are added.
Power Center supports two policy types:
• Static—Manually set the power cap for each device in a rack or chassis.
• Dynamic—Power Center dynamically allocates the power cap for each device in a data center, room, aisle,
rack, or chassis.
From this screen, you can:
• Enable or disable a power policy
• Delete a power policy
• Create a new power policy
• Filter power policies so only certain policies display
• Edit a power policy
• View policy details including:
– Enabled: Whether the policy is enabled or disabled
– Active: Whether the policy is currently in use or not
– Entity Name: Name of the group to which the policy applies
– Policy Name: Name assigned to the policy
– Type: Static policy or dynamic policy
– Power Cap: Power cap for the group
– Date Range: Start and end dates defining when the policy is active
– Time Range: Time of day when the policy is active
– Days: Day(s) of the week when the policy is active
NOTE: If an emergency occurs—for example, power fails and devices are running on the UPS—you can initiate an
Emergency Power Reduction to minimize power consumption.