Owner's Manual

When the average power exceeds this setting, the critical-level event “Average Power” is sent.
Warning Threshold (BTU/hr) for Custom Max Power Group
When the maximum power exceeds this setting, the warning-level event “Max Power” is sent.
Warning Threshold (BTU/hr) for Custom Average Power Group
When the average power exceeds this setting, the warning-level event “Average Power” is sent.
6. Click Apply.
After you configure the thresholds, you can view a graphical representation of the power details in the Power tab.
For more information on configuring the device/group range and sampling interval, see Monitoring Settings.
For more information on configuring default units and energy consumption, see Energy Consumption Settings.
Viewing Power Details
Click Groups in the left pane. Click the icon for the group or device, then open the Power tab.
The Power Details page displays information for PDU and other devices and groups. Power Center does not provide
power details for UPS.
For devices and groups (excluding PDU and UPS), by default, the Power Details graph displays the power details for the
previous hour.
You can also view the following details:
Power Details for the Current Time Window
You can view power details for the current time window by clicking a time window tab. The following table describes the
time windows and their associated intervals:
Table 5. Time Windows and Intervals
Time Window Description Interval
15Min 15 minutes 1 minute
1H 1 hour 3 minutes
1D 1 day 1 hour
1W 1 week 6 hours
1M 1 month 1 day
3M 3 months 1 week
1Y 1 year 2 weeks
NOTE: This table lists the interval when the sampling interval is at the default value (1 minute). Changing the sample
interval results in interval changes for the 15Min and 1H time windows. If you change the sampling interval to 3
minutes, the interval of the 15Min time window is 3 minutes. If you change the sampling interval to 6 minutes, the
interval of the 15Min time window is 3 minutes and the interval of the 1H time window is 6 minutes.