Installation guide
28 | Install the S6000
www.dell.com | support.dell.com
Attaching the Ground Cable
To attach the ground cable to the chassis, use a single M4x0.7 screw. The cable itself is not included with
the S6000. To properly ground the chassis, Dell Networking recommends using a 6AWG one-hole lug,
#10 hole size, 63" spacing (not included in shipping). The one-hole lug must be a UL recognized, crimp-
type lug.
To connect the ground cable to the system, follow these steps:
CAUTION: Grounding conductors must be made of copper. Do not use aluminum conductors.
NOTE: The rack installation “ears” are not suitable for grounding.
NOTE: Coat the one-hole lug with an anti-oxidant compound prior to crimping. Also, bring any un-plated
mating surfaces to a shiny finish and coat with an anti-oxidant prior to mating. Plated mating surfaces must be
clean and free from contamination.