White Papers

vStart 50 VMware vSphere Solution Overview
Dell Inc. 16
Ability to launch iDRAC console from Dell Management Plug-in for vCenter
For more information, see the Embedded Server Management web site.
7 Cooling, Power, and Weight Requirements
This section provides power, cooling, and weight requirements for the solution. Power values provided
in the table are estimated maximum power values for the solution based on Dell Labs measurements.
Actual power, cooling, and weight will vary based on configuration, workload, and Data Center
Environment. PDUs and UPS(s) utilized in this paper are specifically for the solution available in the
USA. Consult with your Dell Sales and Services representatives for further details.
vStart 50 Cooling, Power, and Weight Requirements Table 4.
Solutions
Power
(max watts)
Cooling
(BTU/hr)
Weight (kg)
vStart 50
no UPS
2414
8237
240
with R3750 UPS
2789
9516
305
vStart 50+
no UPS
3114
10625
272
with R3750 UPS
3489
11905
338