Reference Guide

Depende
ncy
Enable System.Power.Cap.Enable
System.Power.Redundancypolicy (Read or Write)
Description Selects the redundancy policy.
Legal Values
N/A
Not Redundant — In this mode, even if one PSU stops
functioning, the server is automatically turned off.
A/C Input Redundant — In this mode, the system is
functional even if one PSU input circuit stops functioning,
provided the PSUs are connected to different input
circuits. This is also called AC redundancy.
PSU Redundant — Available only on systems with four
PSUs. This is also called DC redundancy. This is only valid
in a 2+1 PSU configuration. In this mode, the system is
functional even if one PSU stops functioning.
Default
Value
N/A
Write
Privilege
Login and configure iDRAC
License
Required
iDRAC Express or iDRAC Enterprise
Dependency None
NOTE: In a two PSU system, you must set the primary PSU (that must be
ON). In a four PSU system, you must set the pair of PSUs (1+3 or 2+4)
that must be ON.
System.Power.Cap.Watts (Read or Write)
Descripti
on
Represents the Maximum Power in Watts a device is allowed to
consume. To meet this capacity , throttle the device.
NOTE: This value is applicable only if
System.Power.Cap.Enable is set to 1.
Legal
Values
Values 0–100