Reference Guide
Depende
ncy
Enable System.Power.Cap.Enable
System.Power.Redundancypolicy (Read or Write)
Description Selects the redundancy policy.
Legal Values
• N/A
• Not Redundant — In this mode, even if one PSU stops
functioning, the server is automatically turned off.
• A/C Input Redundant — In this mode, the system is
functional even if one PSU input circuit stops functioning,
provided the PSUs are connected to different input
circuits. This is also called AC redundancy.
• PSU Redundant — Available only on systems with four
PSUs. This is also called DC redundancy. This is only valid
in a 2+1 PSU configuration. In this mode, the system is
functional even if one PSU stops functioning.
Default
Value
N/A
Write
Privilege
Login and configure iDRAC
License
Required
iDRAC Express or iDRAC Enterprise
Dependency None
NOTE: In a two PSU system, you must set the primary PSU (that must be
ON). In a four PSU system, you must set the pair of PSUs (1+3 or 2+4)
that must be ON.
System.Power.Cap.Watts (Read or Write)
Descripti
on
Represents the Maximum Power in Watts a device is allowed to
consume. To meet this capacity , throttle the device.
NOTE: This value is applicable only if
System.Power.Cap.Enable is set to 1.
Legal
Values
Values 0–100
269