36 | Installing DC Power Supplies
www.dell.com | support.dell.com
Figure 8-3. E1200 PEM Front Panel
Cable and Connector Requirements
You must provide your own cables to connect to a remote power source (for example, a circuit breaker
panel) in your equipment rack or office. Cables must be sized to meet the following criteria:
rated for at least 150A service to allow for a fully loaded E1200 system at low input voltage per your
local electrical codes
limits voltage drop across the cable length to 0.5V or less
Before you make the cable connections, apply a coat of antioxidant paste to un-plated metal contact
surfaces. File un-plated connectors, braided straps, and bus bars to a shiny finish. It is not necessary to
file and coat tinned connectors or other plated connection surfaces, such as on the E1200 PEM studs.
Installing DC PEMs
CAUTION: Provide an easily accessible external disconnect. Dell Force10 recommends that you use a 150A
circuit breaker.
CAUTION: Un interrupteur externe doit être fournis et doit être facilement accessible. Dell Force10
recommande l'utilisation d'un disjoncteur de 150Ampères. Eine leicht zugängliche Trennvorrichtung muss in
der.
CAUTION: Verdrahtung eingebaut sein. Dell Force10 empfiehlt, dass Sie einen 150A Sicherungsautomaten
benutzen.
Each E1200 system requires at least one load-sharing DC PEM to operate. Two units are recommended
for full facility redundancy.
Parameter Specifications
Maximum DC PEM Input Current 150A
Maximum Power Dissipation 6850W (21,598 BTU/hour)
CC-E1200-PWR-DC
-48/-60Vdc
150A, 7200VA
Status
Latch Release
PEM interlock
lever
Over-current protector
Locking screws
Studs
FN00102lp