Owners Manual
Wiring instructions for a DC power supply unit
Your system supports up to two –(48–60) V DC power supply units (PSUs).
WARNING: For equipment using –(48–60) V DC power supply units (PSUs), a qualied electrician must perform all connections
to DC power and to safety grounds. Do not attempt connecting to DC power or installing grounds yourself. All electrical wiring
must comply with applicable local or national codes and practices. Damage due to servicing that is not authorized by Dell EMC is
not covered by your warranty. Read and follow all safety instructions that came with the product.
CAUTION: Wire the unit with copper only, unless otherwise specied, use only 10 American Wire Gauge (AWG) wire rated
minimum 90ºC for source and return. Protect the –(48–60) V DC (1 wire) with a branch circuit over-current protection rated 50
A for DC with a high interrupt current rating.
CAUTION: Connect the equipment to a –(48–60) V DC supply source that is electrically isolated from the AC source (reliably
grounded –(48–60) V DC SELV source). Ensure that the –(48–60) V DC source is eciently secured to earth (ground).
NOTE: A readily accessible disconnect device that is suitably approved and rated shall be incorporated in the eld wiring.
Input requirements
• Supply voltage: –(48–60) V DC
• Current consumption: 32 A (maximum)
Kit contents
• Dell EMC part number 6RYJ9 terminal block or equivalent (1)
• #6-32 nut equipped with lock washer (1)
Required tools
Wire-stripper pliers capable of removing insulation from size 10 AWG solid or stranded, insulated copper wire.
NOTE
: Use alpha wire part number 3080 or equivalent (65/30 stranding).
Required wires
• One UL 10 AWG, 2 m maximum (stranded) black wire [–(48–60) V DC].
• One UL 10 AWG, 2 m maximum (stranded) red wire (V DC return).
• One UL 10 AWG, 2 m maximum, green with a yellow stripe, stranded wire (safety ground).
Assembling and connecting safety ground wire
Prerequisite
WARNING
: For equipment using –(48–60) V DC power supply units (PSUs), a qualied electrician must perform all connections
to DC power and to safety grounds. Do not attempt connecting to DC power or installing grounds yourself. All electrical wiring
must comply with applicable local or national codes and practices. Damage due to servicing that is not authorized by Dell EMC is
not covered by your warranty. Read and follow all safety instructions that came with the product.
Installing and removing system components 119