Deployment Guide
The adjustment range of the rail kit from the front post to the rear post is 660 mm–840 mm. This range suits a one-meter deep rack
within Rack Specification IEC 60297.
1. To facilitate access, remove the door from the rack.
2. Ensure that the preassembled rails are at their shortest length.
NOTE: See the reference label on the rail.
3. Locate the rail location pins inside the front of the rack, and extend the length of the rail assembly to position the rear location pins.
Ensure that the pins are fully inserted in the square or round holes in the rack posts.
Figure 12. Secure brackets to the rail (left hand rail shown for 5U84 enclosure)
Item
Description Item Description
1 Fastening screws (A) 8 Front rack post (square hole)
2 Left rail 9 Middle slide locking screws
3 Rear rack post (square hole) 10 5U84 chassis section shown for reference
4 Clamping screw (B) 11 Fastening screw (C)
5 Clamping screw (B) 12 Key: Rail kit fasteners used in rackmount installation
6 Rail location pins (quantity 4 per rail) (A= fastening; B= clamping; C= fastening)
7 5U84 chassis section shown for reference
4. Fully tighten all clamping screws and middle slide locking screws.
5. Ensure the four rear spacer clips (not shown) are fitted to the edge of the rack post.
6. Slide the enclosure until fully seated on its rails.
7. Fasten the front of the enclosure using the enclosure fastening screws (x4) as shown in Figure 12. Secure brackets to the rail (left
hand rail shown for 5U84 enclosure) on page 17.
8. Fix the rear of the enclosure to the sliding bracket with the rear enclosure fastening screws.
CAUTION:
Once the enclosure is installed in the rack, dispose of the lifting straps. The straps cannot be used to remove
the enclosure from the rack.
Reinsert the rear panel modules and install the DDICs into the drawers. See the instructions in the Dell EMC PowerVault ME4 Series
Storage System Owner’s Manual.
• Installing a controller module
• Installing an IOM
• Installing a fan cooling module
• Installing a PSU
• Installing a DDIC
Mount the enclosures in the rack
17