CLI Guide
Table 105. sensors properties (continued)
Name Type Description
• 0: B
• 1: A
• 2: both
• N/A
sensor-name string Sensor name and location.
value string
• For a sensor, its value.
• For overall unit status, one of the status values below.
status string
• OK : The sensor is present and detects no error condition.
• Warning : The sensor detected a non-critical error condition. Temperature,
voltage, or current is between the warning and critical thresholds.
• Critical : The sensor detected a critical error condition. Temperature, voltage, or
current exceeds the critical threshold.
• Unavailable : The sensor is present with no known errors, but has not been
turned on or set into operation because it is initializing. This typically occurs during
controller startup.
• Unrecoverable : The enclosure management processor (EMP) cannot
communicate with the sensor.
• Unknown : The sensor is present but status is not available.
• Not Installed : The sensor is not present.
• Unsupported : Status detection is not implemented.
status-numeric uint32 Numeric equivalents for status values.
• 0: Unsupported
• 1: OK
• 2: Critical
• 3: Warning
• 4: Unrecoverable
• 5: Not Installed
• 6: Unknown
• 7: Unavailable
sensor-location uint32 Superseded by the container property.
container string Hardware component that contains the sensor.
• controllers
• enclosures
• fan
• iom
• midplane
• power-supplies
container-numeric uint32 Numeric equivalents for container values.
• 17: enclosures
• 18: midplane
• 19: controllers
• 20: iom
• 21: power-supplies
• 22: fan
sensor-type string
• Temperature
API basetype properties 391