Users Guide

Table 8. Power Center events and severity levels
Type Description Severity Level
Blades Change In Chassis Some blades in a chassis have changed;
you must manually rediscover the
chassis. Power Center detects chassis
changes once every 15 minutes
Informative
Cannot Register for Events The device cannot register device
events to the Power Center server
automatically.
Warning
Chassis Power Control Capabilities
Changed
The circuit braker power control (system
input power cap) capability on the
chassis no longer exist.
Critical
CMC SNMP Event Event received from chassis Critical or Warning
Communication with Chassis Failed Power Center lost communication with
the chassis.
Warning
Communication with Chassis Restored Power Center restored communication
with the chassis.
Informative
Communication with Device Failed Power Center lost communication with
the device.
Warning
Communication with Device Restored Power Center restored communication
with the device.
Informative
Device Hostname Changed Device hostname is changed. Informative
Entity Capabilities Changed Entity capabilities changed. Warning
Failed to Set Sampling Interval on Device Failed to set sampling interval for the
device. The sample interval might not be
supported by device.
Warning
iDRAC SNMP Event Event received from iDRAC. Critical or Warning
IPMI Fan Events related to the server fan. Critical
IPMI Power Supply Events related to the server. Critical
IPMI Power Unit Events related to the server power unit. Critical
IPMI Processor Temperature Trip Events related to the server processor
temperature trip.
Critical
IPMI Test An IPMI test event was received. Informative
MPCM Configure Failed Failed to set MPCM on the chassis. Warning
MPCM Not Supported The Dell chassis does not support
MPCM. Upgrading firmware on the
chassis might be required.
Warning
PDU High Load The PDU power is greater than the high
load threshold.
Warning
90 Event Management