Temperature-Triggered Policy
18 Static Power and Temperature-Triggered Policies with OpenManage Enterprise Power Manager
Note: Both static and physical groups monitored in Power Manager are available for selection by default.
Location details are displayed only for physical groups with group tag as Room, Aisle or Rack.
Select Static or Physical Group to create Temperature-Triggered policy
Note: Temperature-Triggered policy is supported only for groups monitored by Power Manager and if there is
a minimum of one device added in the group.
Note: If a Temperature-Triggered policy is already created for the group, you cannot create another
Temperature-Triggered policy for that group.
6. In Policy Settings, refer the Temperature data section to configure the temperature threshold value.
Based on the selection of Monitoring time period value, the temperature details are displayed for
selected group.
Select any of the ASHRAE recommended values or a custom value from the Temperature
Threshold drop-down menu.
7. Available ASHRAE recommendations in the drop-down menu are as follows.
• ASHRAE Recommended - 27 degrees Celsius or 81 degrees Fahrenheit
• ASHRAE Class A1 Allowable - 32 degrees Celsius or 90 degrees Fahrenheit
• ASHRAE Class A2 Allowable - 35 degrees Celsius or 95 degrees Fahrenheit
• ASHRAE Class A3 Allowable - 40 degrees Celsius or 104 degrees Fahrenheit
• ASHRAE Class A4 Allowable - 45 degrees Celsius or 113 degrees Fahrenheit