Emergency Power Reduction
22 Benchmark the Performance, Reliability and Scalability of Dell EMC OpenManage Enterprise Power Manager
2.0 in Data Center Environment
8.3 Test Results for EPR actions
Test Results for EPR actions for Heterogeneous Large Business Configuration
Devices in Power
Manager
Tested Devices EPR Action Time Taken
8000
400 Servers
Enable EPR Throttle
8 m 30 s
8000
400 Servers
Disable EPR Throttle
5 m 42 s
8000
400 Servers
Enable EPR Shutdown
8 m 18 s
8000
400 Servers
Disable EPR Shutdown
8 m 14 s
CPU Utilization for EPR Actions
Memory Utilization for EPR Actions
0
500000
1000000
1500000
2000000
2500000
3000000
3500000
4000000
Process(taskexecutionservice)\CPU Utilization
Enable EPR Shutdown Disable EPR Shutdown Enable EPR Throttle Disable EPR Throttle
0
500000
1000000
1500000
2000000
2500000
3000000
3500000
4000000
Process(taskexecutionservice)\Totalmemory(kb)
Enable EPR Shutdown Disable EPR Shutdown Enable EPR Throttle Disable EPR Throttle