Environmental specifications
Operating 10 to 80 percent Relative Humidity with 29°C
(84.2°F) maximum dew point.
Maximum vibration
Operating 0.26 Grms at 5 Hz to 350 Hz (all operation
orientations).
Storage 1.88 Grms at 10 Hz to 500 Hz for 15 min (bottom
side of shippment orirentation only).
Maximum shock
Operating Four shock pulses per axis (the positive and negative
x, y and z axes), 24 total shock pulses.
40 G, 2.3 ms for x and y axes.
36 G, 2.3 ms for z axe.
Storage • 71 G, 2 ms pulse shape is Half-Sine (bottom side
of shipping orientation only).
• 15 G, 165 in/sec pulse shape is Square-Wave
(bottom side of shipping orientation only)
Maximum altitude
Operating 3048 m (10,000 ft).
Storage 12,000 m (39,370 ft).
Operating temperature de-rating
Up to 35°C (95°F) Maximum temperature is reduced by 1°C/300 m
(1°F/547 ft) above 950 m (3,117 ft).
35°C to 40°C (95°F to 104°F) Maximum temperature is reduced by 1°C/175 m
(1°F/319 ft) above 950 m (3,117 ft).
40°C to 45°C (104°F to 113°F) Maximum temperature is reduced by 1°C/125 m
(1°F/228 ft) above 950 m (3,117 ft).
Particulate contamination
NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from
particulates and gaseous contamination. If it is determined that levels of particulates or gaseous
pollution are beyond the limits specified below and are the reason for the damage and/or failures
to your equipment, it may be necessary for you to re-mediate the environmental conditions that
are causing the damage and/or failures. Re-mediation of environmental conditions will be the
responsibility of a customer.