Users Guide
Table 58. Enclosure/Chassis Status Screen
Severity Message Cause
Critical Fan <number> is removed. This fan is required for proper cooling of the enclosure/
chassis.
Warning Power supply redundancy is degraded. One or more PSU have failed or removed and the system can
no longer support full PSU redundancy.
Critical Power supply redundancy is lost. One or more PSU have failed or removed and the system is no
longer redundant.
Critical The power supplies are not redundant. Insufficient
resources to maintain normal operations.
One or more PSU have failed or removed and the system lacks
sufficient power to maintain normal operations. This could
cause servers to power down.
Warning The control panel ambient temperature is greater than
the upper warning threshold.
Chassis/Enclosure intake temperature exceeded the warning
threshold.
Critical The control panel ambient temperature is greater than
the upper warning threshold.
Chassis/Enclosure intake temperature exceeded the warning
threshold.
Critical CMC redundancy is lost. CMC no longer redundant. This happens if the standby CMC
is removed.
Critical All event logging is disabled. The Chassis/Enclosure cannot store events to the logs. This
usually indicates a problem with the control panel or control
panel cable.
Warning Log is full. Chassis has detected that only one more entry can be added
to the CEL (hardware log) before it is full.
Warning Log is almost full. Chassis event log is 75% full.
Table 59. Fan Status Screens
Severity Message Cause
Critical Fan <number> RPM is operating less than the lower
critical threshold.
The speed of the specified fan is not sufficient to provide
enough cooling to the system.
Critical Fan <number> RPM is operating greater than the upper
critical threshold.
The speed of the specified fan is too high, usually due to a
broken fan blade.
Table 60. IOM Status Screens
Severity Message Cause
Warning A fabric mismatch detected on I/O module <number>. The IO module fabric does not match that of the server or the
redundant I/O module.
Warning A link tuning failure detected on I/O module <number>. The IO module could not be set to correctly use the NIC on
one or more servers.
Critical A failure is detected on I/O module <number>. The I/O module has a fault. The same error can also happen if
the I/O module is thermal-tripped.
Table 61. iKVM Status Screen
Severity Message Cause
Warning Console is not available for Local KVM. Minor failure, such as corrupted firmware.
Critical Local KVM can not detect any hosts. USB host enumeration failure.
Critical OSCAR, on screen display is not functional for the
Local KVM.
OSCAR failure.
Non- Recoverable Local KVM is not functional, and is powered off. Serial RIP failure or USB host chip failure.
Using LCD Panel Interface 227