Users Guide

. 48: 电源更改的 SEL 事件
电源事件
系统事件日志 (SEL) 条目
DC output under-current直流输出电流过低 An output under current fault detected on power supply <number>.在电源设
<number> 上检测到输出电流过低故障。
Communication failure通信故障 Cannot communicate with power supply <number>.无法与电源设备
<number> 通信。
Communication restored通信已还原 Communication has been restored to power supply <number>.与电源设备
<number> 的通信已还原。
Failure to communicate status data无法传送状态
数据
Cannot obtain status information from power supply <number>.无法从电源设
<number> 获取状态信息。
Status data communication restored状态数据通信
已还原
Power supply <number> status information successfully obtained.已成功获取
电源设备 <number> 的状态信息。
Over/Under-temperature温度过高/过低 The temperature for power supply <number> is outside of range.电源设备
<number> 的温度超出允许范围。
Fan or Airflow error/warning风扇或气流错误/
Fan failure detected on power supply <number>.在电源设备 <number> 上检
测到风扇故障。
Fan speed overridden风扇速度超限 Fan failure detected on power supply <number>.在电源设备 <number> 上检
测到风扇故障。
Manufacturing fault制造故障 Power supply <number> failed.电源设备 <number> 故障。
Microprocessor busy微处理器正忙 Power supply <number> failed.电源设备 <number> 故障。
FRU errorFRU 错误 Power supply <number> failed.电源设备 <number> 故障。
Unacknowledged 110V operation detected检测到未
认可的 110V 工作状态
Power supply low input voltage (110) was asserted.电源设备输入低压 (110)
已确认。
110V operation acknowledged110V 工作状态认可 Power supply low input voltage (110) was de-asserted.电源输入低压 (110)
解除确认。
与电源冗余状态变化相关并记录在 SEL 中的事件包括冗余丢失以及冗余重新获得这适用于配置为电网冗余电源策略或电源设备
冗余电源策略的模块化机柜。下表列出有关电源冗余策略更改的 SEL 条目。
. 49: 电源冗余策略更改的 SEL 事件
电源策略事件
系统事件日志 (SEL) 条目
冗余丢失
Redundancy lost was asserted冗余丢失已确认
冗余恢复
Redundancy lost was de-asserted冗余丢失已解除确认
配置电源预算和冗余
您可以配置整个机箱机箱、服务器、I/O 模块、iKVMCMC 和电源设备的电源预算、冗余和动态电源整个机箱使用六个电源
设备 (PSU)。电源管理服务可优化电源并根据需要为不同模块重新分配电源。
您可以配置以下各项
系统输入功率上限
冗余策略
扩展电源性能
服务器性能优先于电源冗余
动态电源设备接入
禁用机箱电源按钮
允许 110 V 交流操作
最大节能模式
远程电源日志记录
远程电源日志记录间隔
194