Users Guide

Power Supply Event System Event Log (SEL) Entry
Communication failure Cannot communicate with power supply <number>.
Communication restored Communication has been restored to power supply <number>.
Failure to communicate status data Cannot obtain status information from power supply <number>.
Status data communication restored Power supply <number> status information successfully obtained.
Over/Under-temperature The temperature for power supply <number> is outside of range.
Fan or Airow error/warning Fan failure detected on power supply <number> .
Fan speed overridden Fan failure detected on power supply <number> .
Manufacturing fault Power supply <number> failed.
Microprocessor busy Power supply <number> failed.
FRU error Power supply <number> failed.
Unacknowledged 110V operation detected Power supply low input voltage (110) was asserted.
110V operation acknowledged Power supply low input voltage (110) was de-asserted.
Events related to changes in the power redundancy status that record entries in the SEL are redundancy loss and redundancy regain for
the modular enclosure that is congured for either an Grid Redundancy power policy or Power Supply Redundancy power policy. The
following table lists the SEL entries that are related to power redundancy policy changes.
Table 49. SEL Events for Power Redundancy Policy Changes
Power Policy Event System Event Log (SEL) Entry
Redundancy lost Redundancy lost was asserted
Redundancy regained Redundancy lost was de-asserted
Conguring power budget and redundancy
You can congure the power budget, redundancy, and dynamic power of the entire chassis (chassis, servers, I/O modules, iKVM, CMC, and
power supplies), which uses six power supply units (PSUs). The power management service optimizes power consumption and re-allocates
power to dierent modules based on the requirement.
You can congure the following:
System Input Power Cap
Redundancy Policy
Extended Power Performance
Server Performance Over Power Redundancy
Dynamic Power Supply Engagement
Disable Chassis Power Button
Allow 110 VAC Operation
Max Power Conservation Mode
Remote Power Logging
Remote Power Logging Interval
Server Based Power Management
Disable AC Power Recovery
230