CLI Guide
getpminfo
Table 68. Details of getpminfo attribute
Description Displays power management status information.
To run this subcommand, you must have the CMC Login User privilege.
Synopsis
racadm getpminfo
Input N/A
Table 69. Example:
[Real-Time Power Statistics]
System Input Power = 1661 W (5667 BTU/h)
Peak System Power = 1916 W (6537 BTU/h)
Peak System Power Start Time = 09:19:27 11/26/2014
Peak System Power Timestamp = 09:29:20 11/26/2014
Minimum System Power = 35 W (119 BTU/h)
Minimum System Power Start Time = 09:19:27 11/26/2014
Minimum System Power Timestamp = 09:54:00 11/26/2014
System Idle Power = 1661 W (5667 BTU/h)
System Potential Power = 3414 W (11649 BTU/h)
System Input Current Reading = 7.3 A
[Real-Time Energy Statistics]
System Energy Consumption = 1.6 kWh
System Energy Consumption Start Time = 09:19:27 11/26/2014
System Energy Consumption Timestamp = 10:31:42 11/26/2014
[System Power Status]
Chassis Power State = ON
Overall Power Health = OK
Redundancy = No
[System Power Policy Configuration]
System Input Power Cap = 16685 W (56931 BTU/h | 100%)
Redundancy Policy = None
Dynamic PSU Engagement Enabled = No
[Power Budgeting]
System Input Max Power Capacity = 16685 W
56 RACADM Subcommand Details