CLI Guide
Example
• Display the current status of all chassis features:
racadm feature -s
• Deactivate the FlexAddressPlus feature on the chassis:
racadm feature -d -c FlexAddressPlus
featurecard
Table 18. Details of featurecard attribute
Description Veries proper SD card installation and displays the SD card status.
To use this subcommand, you must have the Chassis Conguration Administrator privilege.
Synopsis
racadm featurecard -s
Input
-s — Lists active SD card features and SD card status.
Output
• No feature card inserted — Action: To verify that the SD card was properly inserted, check the CMC.
In a redundant CMC conguration, make sure the CMC with the SD feature card installed is the active CMC and
not the standby CMC.
• The feature card inserted is valid and contains the following feature(s)
FlexAddress: The feature card is bound to this chassis
— Action: No action required.
• No features active on the chassis — Action: Install the SD card into the CMC.
• The feature card inserted is valid and contains the following feature(s)
FlexAddress: The feature card is bound to another chassis, svctag = ABC1234,
SD card SN = 01122334455
Action: Remove the SD card; locate and install the SD card for the current chassis.
• The feature card inserted is valid and contains the following feature(s)
FlexAddress: The feature card is not bound to any chassis
Action: The feature card can be moved to another chassis, or can be reactivated on the current chassis. To
reactivate on the current chassis, enter racadm racreset until the CMC module with the feature card
installed becomes active.
Example
$ racadm featurecard -s
The feature card inserted is valid, serial number TEST0123456789012345678
The feature card contains the following feature(s):
FlexAddress: The feature is bound to this chassis
FlexAddressPlus: The feature is bound to this chassis
ExtendedStorage: The feature is bound to this chassis
fwupdate
Table 19. Details of fwupdate
Description
Allows you to update the rmware on the KVM, active CMC, standby CMC, iDRAC or an IOM infrastructure device.
You can:
• Check the rmware update process status.
• Update CMC from FTP or TFTP server by providing an IP address and optional path.
• Update CMC from the local le system using Remote RACADM.
• There can only be a single update operation in progress at any time. In addition, the fwupdate subcommand may
only update one or more devices of a single kind at a time.
28 RACADM Subcommand Details