Users Guide

Scenario 5: Trying to enable EPP from the disabled start condition, when other power conguration settings are set.
Enabling EPP on a 3000W AC PSU when System Input Power Cap is low
racadm config -g cfgchassispower -o cfgChassisEPPEnable
This feature is not supported while System Input Power Cap is set to less than or
equal to 13300 W (45381 BTU/h).
Enabling EPP on a 3000W AC PSU when DPSE is Enabled
racadm config -g cfgChassisPower -o cfgChassisEPPEnable 1
This feature is not supported while Dynamic Power Supply Engagement is enabled.
Enabling EPP on a 3000W AC PSU when SBPM is Enabled
racadm config -g cfgChassisPower -o cfgChassisEPPEnable 1
This feature is not supported while Server Based Power Management is enabled.
Enabling EPP on a 3000W AC PSU when MPCM is Enabled
racadm config -g cfgChassisPower -o cfgChassisEPPEnable 1
This feature is not supported while Max Power Conservation Mode is enabled.
Enabling EPP on a 3000W AC PSU when PSU Redundancy Policy is set
racadm config -g cfgChassisPower -o cfgChassisEPPEnable 1
This feature is not supported until Redundancy Policy is set to Grid Redundancy.
Enabling EPP on a 3000W AC PSU when No Redundancy Policy is set
racadm config -g cfgChassisPower -o cfgChassisEPPEnable 1
This feature is not supported until Redundancy Policy is set to Grid Redundancy.
Scenario 6: Firmware downgrade when EPP is enabled on a 3000W AC PSUs
racadm fwupdate -g -u -a 192.168.0.100 -d firmimg.cmc -m cmc-active -m cmc-standby
Cannot update local CMC firmware: The uploaded firmware image does not support the
installed power supplies.
243