Users Guide
Table 49. Racadm commands for subsystems
Subsystem RACADM Command
General System/RAC information
getsysinfo
Session information
getssinfo
Sensor information
getsensorinfo
Switches information (IO Module)
getioinfo
Mezzanine card information (Daughter card)
getdcinfo
All modules information
getmodinfo
Power budget information
getpbinfo
KVM information
getkvminfo
NIC information (CMC module)
getniccfg
Redundancy information
getredundancymode
Trace log information
gettracelog
RAC event log
gettraclog
System event log
getsel
Downloading SNMP Management Information Base File
The CMC SNMP Management Information Base (MIB) File denes chassis types, events, and indicators. CMC enables you to
download the MIB le using the Web Interface.
To download the CMC's SNMP Management Information Base (MIB) le using the CMC Web interface:
1. In the system tree, go to Chassis Overview and click Network → Services → SNMP.
The SNMP Conguration section is displayed.
2. Click Save to download the CMC MIB le to your local system.
For more information on the SNMP MIB le, see the Dell OpenManage Server Administrator SNMP Reference Guide at
dell.com/support/manuals.
First Steps to Troubleshoot a Remote System
The following questions are commonly used to troubleshoot high-level problems in the managed system:
• Is the system powered on or o?
• If powered on, is the operating system functioning, crashed, or frozen?
• If powered o, did the power turn o unexpectedly?
Power Troubleshooting
The following information helps you to troubleshoot power supply and power-related issues:
• Problem: Congured the Power Redundancy Policy to Grid Redundancy, and a Power Supply Redundancy Lost event was
raised.
– Resolution A: This conguration requires at least one power supply in side 1 (the left three slots) and one power supply in
side 2 (the right three slots) to be present and functional in the modular enclosure. Additionally the capacity of each side
must be enough to support the total power allocations for the chassis to maintain Grid Redundancy. (For full Grid
Redundancy operation, ensure that a full PSU conguration of six power supplies is available.)
209