Users Guide
5. Click OK to perform the power management action (for example, cause the server to reset).
Executing Power Control Operations on a Server Using RACADM
To execute power control operations on a server using RACADM, open a serial/Telnet/SSH text console to CMC, log in, and type:
racadm serveraction -m <module> <action>
where <module> specifies the server by its slot number (server-1 through server-16) in the chassis, and <action> is the operation
you want to execute: powerup, powerdown, powercycle, graceshutdown, or hardreset.
Executing Power Control Operations on an IOM
You can remotely execute a reset or power cycle on an individual IOM.
NOTE: To perform power management actions, you must have Chassis Configuration Administrator privilege.
Executing Power Control Operations on IOMs Using CMC Web Interface
To execute power control operations on an IOM using the CMC Web interface:
1. In the system tree, go to Chassis Overview → I/O Module Overview and click Power.
The Power Control page is displayed.
2. For the IOM in the list, from the drop-down menu, select the operation you want to execute (reset or power cycle).
3. Click Apply.
A dialog box appears requesting confirmation.
4. Click OK to perform the power management action (for example, cause the IOM to power cycle).
Executing Power Control Operations on IOMs Using RACADM
To execute power control operations on an IOM using RACADM, open a serial/Telnet/SSH text console to CMC, log in, and type:
racadm chassisaction -m switch-<n><action>
where <n> is a number 1-6 and specifies the IOM (A1, A2, B1, B2, C1, C2), and <action> indicates the operation you want to
execute: powercycle or reset.
209