Dynamic PSU Engagement Enabled = No
System Input Max Power Capacity = 16685 W
Input Redundancy Reserve = 0 W
Input Power Allocated to Servers = 1826 W
Input Power Allocated to Chassis
Infrastructure
= 1212 W
Total Input Power Available for
Allocation
= 13648 W
Standby Input Power Capacity = 0 W
Server Based Power Management Mode = No
Max Power Conservation Mode = No
Server Performance Over Power Redundan
cy
= No
Power Available for Server Power-on = 13648 W
Extended Power Performance (EPP)
Status
= Disabled
Available Power in EPP Pool = 0 W (0 BTU/h)
Used Power in EPP Pool = 0 W (0 BTU/h)
EPP Percent - Available = 0.0
[Chassis Power Supply Status Table]
<Name> <Model> <Power State> <Input
Current>
<Input Volts> <Output Rated
Power>
PS1 08V4DK Online 1.0 A 240.0 V 3000 W
PS2 08V4DK Online 1.9 A 239.2 V 3000 W
PS3 08V4DK Online 1.1 A 239.5 V 3000 W
PS4 08V4DK Online 1.1 A 239.5 V 3000 W
PS5 08V4DK Online 1.0 A 239.8 V 3000 W
PS6 08V4DK Online 1.9 A 239.8 V 3000 W
[Server Module Power Allocation Table]
<Slot#> <Server Name> <PowerState> <Allocation> <Priority
>
<Blade Type>
1 SLOT-01 ON 114 W 1 PowerEdge M630
2 WIN-JGKC47ACGKG ON 77 W 1 PowerEdge M630
3 SLOT-03 ON 93 W 1 PowerEdge M630
4 SLOT-04 ON 137 W 1 PowerEdge M630
5 SLOT-05 ON 129 W 1 PowerEdge M630
6 SLOT-06 ON 130 W 1 PowerEdge M630