Users Guide

Executing Power Control Operations on a Server Using RACADM
To execute power control operations on a server using RACADM, open a serial/Telnet/SSH text console
to CMC, log in, and type:
racadm serveraction -m <module> <action>
where <module> specifies the server by its slot number (server-1 through server-16) in the chassis, and
<
action> is the operation you want to execute: powerup, powerdown, powercycle, graceshutdown, or
hardreset.
Executing Power Control Operations on an IOM
You can remotely execute a reset or power cycle on an individual IOM.
NOTE: To perform power management actions, you must have Chassis Configuration
Administrator privilege.
Executing Power Control Operations on IOMs Using CMC Web Interface
To execute power control operations on an IOM using the CMC Web interface:
1. In the system tree, go to Chassis OverviewI/O Module Overview and click Power.
The Power Control page is displayed.
2. For the IOM in the list, from the drop-down menu, select the operation you want to execute (reset or
power cycle).
3. Click Apply.
A dialog box appears requesting confirmation.
4. Click OK to perform the power management action (for example, cause the IOM to power cycle).
Executing Power Control Operations on IOMs Using RACADM
To execute power control operations on an IOM using RACADM, open a serial/Telnet/SSH text console to
CMC, log in, and type:
racadm chassisaction -m switch-<n><action>
where <n> is a number 1-6 and specifies the IOM (A1, A2, B1, B2, C1, C2), and <action> indicates the
operation you want to execute: powercycle or reset.
253