Reference Guide

Fabric A (LOM port)
Fabric B (mezzanine port)
The default is Fabric B. If the option is not specified, then the configuration is not
done.
Output <module> configuration was initiated successfully. It may take several minutes to
complete.
Example
Set member name, member IP, member netmask, member gateway with new group
name, group IP, group password, admin password selecting fabric A on server-1.
racadm setarraycfg -m server-1 -n cmc-col 192.168.1.233
255.255.255.0 192.168.1.0 -e 0 -g cmc-array-grp 192.168.1.10
<password> -f A
Set member name, member IP, member netmask, member gateway with existing
group name, group IP, group password selecting fabric B on server-1.
racadm setarraycfg -m server-1 -n cmc-col 192.168.1.233
255.255.255.0 192.168.1.0 -e 1 -g cmc-array-grp 192.168.1.10
<password> -f B
Select different fabric type.
racadm setarraycfg -m server-3 -f A
setassettag
Description Sets the N-byte ASCII asset tag for the chassis.
To use this subcommand, you must have the Administrator privilege.
NOTE: The special characters “ (double quotation mark), ‘ (backward quotation
mark), & (ampersand), and \ (backward slash) are not supported for this
subcommand.
Synopsis
racadm setassettag -m module <assettag>
Input -m <module> — Specifies the module whose asset tag you want to set.
Legal value: chassis
You can obtain the same output if you do not include this option, as there is only one
legal value.
<assettag> is a maximum of 64 non-extended ASCII characters.
Example
racadm setassettag -m chassis 783839–33
racadm setassettag 783839–33
The asset tag was changed successfully.
setchassisname
Description Sets the name of the chassis in the LCD.
77