Reference Guide
Displays power managemnt status information:
racadm getpminfo
[Real-Time Power Statistics]
System Input Power = 1661 W (5667 BTU/h)
Peak System Power = 1916 W (6537 BTU/h)
Peak System Power Start Time = 09:19:27 11/26/2014
Peak System Power Timestamp = 09:29:20 11/26/2014
Minimum System Power = 35 W (119 BTU/h)
Minimum System Power Start Time = 09:19:27 11/26/2014
Minimum System Power Timestamp = 09:54:00 11/26/2014
System Idle Power = 1661 W (5667 BTU/h)
System Potential Power = 3414 W (11649 BTU/h)
System Input Current Reading = 7.3 A
[Real-Time Energy Statistics]
System Energy Consumption = 1.6 kWh
System Energy Consumption Start Time = 09:19:27 11/26/2014
System Energy Consumption Timestamp = 10:31:42 11/26/2014
[System Power Status]
Chassis Power State = ON
Overall Power Health = OK
Redundancy = No
[System Power Policy Configuration]
System Input Power Cap = 16685 W (56931 BTU/h | 100%)
Redundancy Policy = None
Dynamic PSU Engagement Enabled = No
[Power Budgeting]
System Input Max Power Capacity = 16685 W
Input Redundancy Reserve = 0 W
Input Power Allocated to Servers = 1875 W
Input Power Allocated to Chassis
Infrastructure
= 1402 W