Reference Guide

cfgChassisPowerCapBTU (Read or Write)
Description
Indicates the maximum power consumption limit (in BTU/hr) for the entire chassis. The
command generates an error if server throttling is necessary to achieve the power goal
based on the value for this setting.
Legal Values
9264–56931 BTU/hr
Default
43221 BTU/hr
cfgChassisPowerCapFBTU (Read or Write)
Description
Indicates the maximum power consumption limit (in BTU/hr) for the entire chassis. Use
cfgChassisCapFBTU when power consumption changes regardless of whether server
throttling is required. The command generates an error if the value for this setting is
lower than the minimum power required for the chassis configuration.
Legal Values
9264–56931 BTU/hr
Default
56931 BTU/hr
cfgChassisPowerCapPercent (Read or Write)
Description
Indicates the power consumption limit as a percentage. The percentage is computed
mathematically as the minimum power + (percent * (maximum power — minimum
power)). The command generates an error if server throttling is necessary to achieve the
power goal based on the value for this setting.
Legal Values
16–100
NOTE: If the specified percent is lower than the minimum value, the CMC sets the
value to the minimum value.
Default
100
cfgChassisPowerCapFPercent (Read or Write)
Description
Indicates the power consumption limit as a percentage. The percentage is computed
mathematically as the minimum power + (percent * (maximum power — minimum
power)). Use cfgChassisPowerCapFPercent when power consumption is changes
regardless of whether server throttling is required.
Legal Values
16–100
NOTE: If the specified percent is lower than the minimum value, the CMC sets the
value to the minimum value.
Default
100
139