Users Guide

3000W 交流 PSU 上启用动态电源设备接入
racadm config -g cfgChassisPower -o cfgChassisDynamicPSUEngagementEnable 1
This feature is not supported while Extended Power Performance is enabled.
将电源冗余策略从电网冗余策略更改为 3000W 交流 PSU 上的 PSU 冗余策略
racadm config -g cfgChassisPower -o cfgChassisRedundancyPolicy 2 This
feature is not supported while Extended Power Performance is enabled.
将电源冗余策略从电网冗余策略更改为 3000W 交流 PSU 上的无冗余策略
racadm config -g cfgChassisPower -o cfgChassisRedundancyPolicy 0 This
feature is not supported while Extended Power Performance is enabled.
将系统输入功率上限值更改为小于或等于 13300 W
racadm config g cfgChassisPower -o cfgChassisPowerCap 12500 System Input
Power Cap cannot be set to less than or equal to 13300W (45381 BTU/h) while
Extended Power Performance is enabled.
3000W 交流 PSU 上启用 110V(交流)
racadm config -g cfgChassisPower -o cfgChassisAllow110VACOperation 1 This
feature is not supported on 3000W power supplies.
3000W 交流 PSU 上启用最大节能模式
:
RACADM CLI 结合现有界面使用,可在 3000W 交流 PSU 配置上启用最大节能模式 (MPCM)。如果启
用了 EPP,启用 MPCM 时无需更改 RACADM CLI 界面。
场景 5:当设置了其他电源配置设置时,尝试从已禁用的开始状态下启用 EPP
在系统输入功率上限较低时在 3000W 交流 PSU 上启用 EPP
racadm config -g cfgchassispower -o cfgChassisEPPEnable This feature is not
supported while System Input Power Cap is set to less than or equal to 13300
W (45381 BTU/h).
在启用了 DPSE 后在 3000W 交流 PSU 上启用 EPP
racadm config -g cfgChassisPower -o cfgChassisEPPEnable 1 This feature is
not supported while Dynamic Power Supply Engagement is enabled.
在启用了 SBPM 后在 3000W 交流 PSU 上启用 EPP
racadm config -g cfgChassisPower -o cfgChassisEPPEnable 1 This feature is
not supported while Server Based Power Management is enabled.
在启用了 MPCM 后在 3000W 交流 PSU 上启用 EPP
racadm config -g cfgChassisPower -o cfgChassisEPPEnable 1 This feature is
not supported while Max Power Conservation Mode is enabled.
在设置了 PSU 冗余策略后在 3000W 交流 PSU 上启用 EPP
racadm config -g cfgChassisPower -o cfgChassisEPPEnable 1 This feature is
not supported until Redundancy Policy is set to Grid Redundancy.
在设置了无冗余策略后在 3000W 交流 PSU 上启用 EPP
racadm config -g cfgChassisPower -o cfgChassisEPPEnable 1 This feature is
not supported until Redundancy Policy is set to Grid Redundancy.
场景 6:在 3000W 交流 PSU 上启用了 EPP 后固件降级
racadm fwupdate -g -u -a 192.168.0.100 -d firmimg.cmc -m cmc-active -m cmc-
standby Cannot update local CMC firmware: The uploaded firmware image does not
support the installed power supplies.
255