Reference Guide

Display iDRAC network settings in server slot 1
racadm getniccfg -m server-1
getpbinfo
Description Displays power budget status information.
To run this subcommand, you must have the CMC Login User privilege.
Synopsis
racadm getpbinfo
Input N/A
Example
Displays power budget status information
racadm getpbinfo
[Power Budget Status]
System Input Power = 1574 W
Peak System Power = 1916 W
Peak System Power Timestamp = 09:29:20 11/26/2014
Minimum System Power = 374 W
Minimum System Power Timestamp = 09:20:51 11/26/2014
Overall Power Health = OK
Redundancy = No
System Input Power Cap = 16685 W
Redundancy Policy = None
Dynamic PSU Engagement Enabled = No
System Input Max Power Capacity = 16685 W
Input Redundancy Reserve = 0 W
Input Power Allocated to Servers = 1826 W
Input Power Allocated to Chassis
Infrastructure
= 1212 W
Total Input Power Available for
Allocation
= 13648 W
Standby Input Power Capacity = 0 W
Server Based Power Management Mode = No
Max Power Conservation Mode = No
Server Performance Over Power Redundan
cy
= No
Power Available for Server Power-on = 13648 W
Extended Power Performance (EPP)
Status
= Disabled
46