Severity Message Cause
Critical The power supplies are not redundant.
Insufficient resources to maintain normal
operations.
One or more PSU have failed or removed and the
system lacks sufficient power to maintain normal
operations. This could cause servers to power down.
Warning The control panel ambient temperature is
greater than the upper warning threshold.
Chassis/Enclosure intake temperature exceeded the
warning threshold.
Critical The control panel ambient temperature is
greater than the upper warning threshold.
Chassis/Enclosure intake temperature exceeded the
warning threshold.
Critical CMC redundancy is lost. CMC no longer redundant. This happens if the standby
CMC is removed.
Critical All event logging is disabled. The Chassis/Enclosure cannot store events to the
logs. This usually indicates a problem with the control
panel or control panel cable.
Warning Log is full. Chassis has detected that only one more entry can be
added to the CEL (hardware log) before it is full.
Warning Log is almost full. Chassis event log is 75% full.
Table 44. Fan Status Screens
Severity Message Cause
Critical Fan <number> RPM is operating less than the
lower critical threshold.
The speed of the specified fan is not sufficient to
provide enough cooling to the system.
Critical Fan <number> RPM is operating greater than the
upper critical threshold.
The speed of the specified fan is too high, usually due
to a broken fan blade.
Table 45. IOM Status Screens
Severity Message Cause
Warning A fabric mismatch detected on I/O module
<number>.
The IO module fabric does not match that of the
server or the redundant I/O module.
Warning A link tuning failure detected on I/O module
<number>.
The IO module could not be set to correctly use the
NIC on one or more servers.
Critical A failure is detected on I/O module <number>. The I/O module has a fault. The same error can also
happen if the I/O module is thermal-tripped.
Table 46. iKVM Status Screen
Severity Message Cause
Warning Console is not available for Local KVM. Minor failure, such as corrupted firmware.
Critical Local KVM can not detect any hosts. USB host enumeration failure.
Critical OSCAR, on screen display is not functional
for the Local KVM.
OSCAR failure.
Non- Recoverable Local KVM is not functional, and is powered
off.
Serial RIP failure or USB host chip failure.