Owner's Manual
366 Power Management
Using the Web Interface
To enable PM3 external management:
1
Login with
Chassis Configuration Administrator
privileges to the chassis.
2
Select
Chassis Overview
in the system tree.
3
Click
Power
Configuration
.
The
Budget/Redundancy Configuration
page is displayed.
4
Set
Server Based Power Management Mode
.
5
Click
Apply
.
After the Server Based Power Management Mode is enabled, the chassis is
prepared for PM3 management. All 12th generation server priorities are set to
1 (High). PM3 manages the server power and priorities directly. Since PM3
controls compatible server power allocations, CMC no longer controls the
Maximum Power Conservation Mode. Hence this selection is disabled.
When the Maximum Power Conservation Mode is enabled, the CMC sets
the System Input Power Capacity to the maximum that the chassis can
handle. CMC does not allow power to exceed the highest capacity. However,
PM3 handles all other power capacity limitations.
To disable external power management:
1
Login with
Chassis Configuration Administrator
privileges to the chassis.
2
Select
Chassis Overview
in the system tree.
3
Click
Power
Configuration
.
The
Budget/Redundancy Configuration
page displays.
4
Clear
Server Based Power Management Mode
.
5
Click
Apply
.
When PM3 management of power is disabled, the CMC reverts to the server
priority settings before the external management was enabled.
NOTE: When PM3 management is disabled, CMC does not revert to the earlier
setting of the maximum chassis power. Refer to the CMC log for the earlier setting in
order to manually restore the value.