Quick Reference Guide

-E — Displays RAW SEL data with the other data
for each entry.
-R — Displays only RAW SEL data for each entry.
This option is not applicable to CMC.
-i — Displays the number of entries in the SEL.
This option is not applicable to CMC.
--more — Displays one screen at a time and
prompts the user to continue (similar to the UNIX
more command.)
Output Record: 12
Date/Time: 11/20/2011 14:19:34
Source: system
Severity: Ok
Description: C: boot completed.
Example
racadm getsel
getsensorinfo
Description Displays status for system sensors.
To use this subcommand, you must have CMC Login User
privilege.
Synopsis
racadm getsensorinfo
Examples
racadm getsensorinfo
<senType> <Num> <sensorName> <status> <reading>
<units> <lc> <uc>
FanSpeed 1 Fan-1 OK 4768 rpm 2344 14500
FanSpeed 2 Fan-2 OK 4873 rpm 2344 14500
FanSpeed 3 Fan-3 OK 4832 rpm 2344 14500
FanSpeed 4 Fan-4 OK 4704 rpm 2344 14500
FanSpeed 5 Fan-5 OK 4833 rpm 2344 14500
FanSpeed 6 Fan-6 OK 4829 rpm 2344 14500
FanSpeed 7 Fan-7 OK 4719 rpm 2344 14500
FanSpeed 8 Fan-8 Not OK 1 rpm 2344 14500
FanSpeed 9 Fan-9 OK 4815 rpm 2344 14500
<
senType> <Num> <sensorName> <status> <reading> <units> <lc>
63